Technical Specifications
Property | Unit | Test Method | Value | |
---|---|---|---|---|
Density | +23C | g/cm3 | ISO 1183 | 0,909 |
Melting Flow Rate | MFR 190/5 MFR 230/2,16 MFR 230/5 |
g/10 min g/10 min g/10 min |
ISO 1133 ISO 1133 ISO 1133 |
0,55 0,30 1,20 |
Volume Flow Rate | MFR 230/2,16 | cm3/10 min | ISO 1133 | 0,4 |
Tensile Strength | (50 mm/min) | MPa | ISO 527/1+2 | 25 |
Elongation Rate | (50 mm/min) | % | ISO 527/1+2 | 600 |
Shore D Rigidity | (3 sec value) | DIN 53505 | 65 | |
Charpy notch (Resistance) |
+23°C 0°C -30°C |
kJ/m² kJ/m² kJ/m² |
ISO 179/1eU ISO 179/1eU ISO 179/1eU |
43 43 43 |
Charpy Notch Impact Resistance |
+23°C 0°C -30°C |
kJ/m² kJ/m² kJ/m² |
ISO 179/1eA ISO 179/1eA ISO 179/1eA |
52 7 2,5 |
Vicat Softening Point | VST/A/ 50 VST/B/ |
°C °C |
ISO 306 ISO 306 |
132 69 |
Melting Interval | °C | DSC | 150-160 | |
Linear Thermal Expansion Co-efficient | 1/K | DIN 53752 | 0,030 | |
Thermal Conductivity | W/mK | DIN 52612 | 0,24 | |
Surface Resistance | 0hm | DIN VDE 0303,T3 | >1014 |
Standard Number TS EN ISO 15874-2 | ||||
---|---|---|---|---|
Standard Name | Plastic Piping Systems – For Hot and Cold Water – Polypropylene [PP] – Section: 2 Pipes | |||
Tests | 1- Mechanical Properties | |||
Hydrostatic Tension(MPa) | Test Temperature ("C) | Test Duration(Hour) | Test Presssure (Bar) | |
16 | 20 | 1 | 65 | |
4.3 | 95 | 22 | 18 | |
3.8 | 95 | 165 | 15 | |
3.5 | 95 | 1000 | 14 | |
2- Physical and Chemical Properties | ||||
Requirement | Parameter | Duration (Hour) | ||
Dimensional Stability | <%2 | 135 °C | en > 8 mm →1 | |
8 mm < en < 16 mm → 2 | ||||
en > 16 mm → 4 | ||||
Thermal Stability with Hydrostatic Pressure Test | No bursting during the test. | 110 °C - 1,9 MPa | 8760 | |
Impact Resistance | <%10 | 0 °C - 10 Parça | en < 8,6 mm → 1 | |
8,6 mm < en <14,1 mm →2 | ||||
en > 14,1 mm → 4 | ||||
MFI (Raw material) | < 0,5 gr / 10 dk | 230 °C - 2,16 kg | ||
MFI (Pipe) | When compared with raw material, the measured difference should be max. 30%. | 230 °C - 2,16 kg |